Permit: T16BU01173

Parcel: 140420740


Addresses:

7250 S TUCSON BL

Inspection Status: Closed

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
10/13/2022 FIRE SPKLR - FINAL Closed PERMIT CLOSED CONTRACTOR DID NOT CALL IN INSPECTION. SYSTEM NOT VERIFIED.
11/08/2017 FIRE SPKLR - FINAL Continued The two back flow preventer OS&Y valves and the Hugenot tamper switch need to be electronically supervised by the fire alarm system in the East and West riser rooms. Fire alam permit will be required. Need to add heads in the attached/adjacent electrical equipment rooms for proper coverage.