Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T16BU01037
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | passed hydro 200 lbs for 2 plus hrs, visualized tracer wire and mega lugged connections, wrapped connections. Must have NFPA 24 paperwork and tracer wire to follow up C900 stub up. |