Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T16BU01027
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2016 | FIRE SPKLR - FINAL | Approved | ||
08/09/2016 | FIRE SPKLR - FINAL | Denied | 1) Need coverage under HVAC ducts over 4'. 2) Uprights too far off rear wall. 3) Verify upright coverage over drop ceiling in rear. 4) Drawing not correct. Submit as builts. |