Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T16BU00967

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2016 FIRE - ALARM FINAL Approved
11/02/2016 FIRE - ALARM FINAL Partial Approval Waiting on intelligibility report from redhawk.
10/28/2016 FIRE - ALARM FINAL Partial Approval need to provide the inteligability test
provide monitoring paperwork
provide proof of UL and FM
Theater 12, 13 and 14 projector did not operate
Kitchen system tested via short, needs complete test
10/25/2016 FIRE - ALARM FINAL Partial Approval Check the audibility and intelligibility of the voice evac speakers. Provide documentation showing meets the minimum code requirements.

Smoke detector above the RAAN - provide documentation regarding the reflective ceiling plan and proper spacing.

Provide monitoring station UL and or FM certificate.

manually verified the flow switch due to the water not being turned on. Need to verify with fire sprinkler final.

Phone line 2 is showing a comm fail, check the long distance on phone line

Provide documentation from central station for signals received.

All speakers, speaker strobes and strobes to be mounted at a minimum 80" to the bottom of the lens...locations to be corrected.

Theater 5

South corridor exit

South corridor bathroom

Outside theater 7

Stage room south corner back exit

womens bathroom south

mens bathroom south

Side by 7

Starcade

Foyer

Box office x 2

Extreme digital x 2

Theater 14 front

Managers office x 2

North corridor x 2

Mens bathroom north

Womens bathroom north

Theater 10 by door

Connect the ansul system with the fire alarm

Need to verify the shout down of projectors.