Inspection History: FIRE - ALARM FINAL
Permit Number - T16BU00967
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/08/2016 | FIRE - ALARM FINAL | Approved | ||
11/02/2016 | FIRE - ALARM FINAL | Partial Approval | Waiting on intelligibility report from redhawk. | |
10/28/2016 | FIRE - ALARM FINAL | Partial Approval | need to provide the inteligability test provide monitoring paperwork provide proof of UL and FM Theater 12, 13 and 14 projector did not operate Kitchen system tested via short, needs complete test |
|
10/25/2016 | FIRE - ALARM FINAL | Partial Approval | Check the audibility and intelligibility of the voice evac speakers. Provide documentation showing meets the minimum code requirements. Smoke detector above the RAAN - provide documentation regarding the reflective ceiling plan and proper spacing. Provide monitoring station UL and or FM certificate. manually verified the flow switch due to the water not being turned on. Need to verify with fire sprinkler final. Phone line 2 is showing a comm fail, check the long distance on phone line Provide documentation from central station for signals received. All speakers, speaker strobes and strobes to be mounted at a minimum 80" to the bottom of the lens...locations to be corrected. Theater 5 South corridor exit South corridor bathroom Outside theater 7 Stage room south corner back exit womens bathroom south mens bathroom south Side by 7 Starcade Foyer Box office x 2 Extreme digital x 2 Theater 14 front Managers office x 2 North corridor x 2 Mens bathroom north Womens bathroom north Theater 10 by door Connect the ansul system with the fire alarm Need to verify the shout down of projectors. |