Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG PIPING FLUSH
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2016 | FIRE SPKLR - UG PIPING FLUSH | Approved | Flushed clear for 1 1/2 minutes with burlap. No rocks or debris in bag. Until NFPA24 paperwork recieved, no Fire sprinkler final shall be given. |