Permit: T16BU00934

Parcel: 13615041A

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T16BU00934

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/28/2017 FIRE SPKLR - FINAL Approved Need to order Knox cap
02/23/2017 FIRE SPKLR - FINAL Not ready for Inspection All ceiling tiles need to be installed.
Bell for sprinkler system must be installed, tested.
Install 200^ sprinkler in freezer area.
Relocate sprinkler to north of hood so not blocked.
Order locking FDC cap and lock box for west entry.