Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2016 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 06/24/2016 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1. Pressure not at 200psi. Was at roughly 180psi. | |
| 06/23/2016 | FIRE SPKLR - OH PIPING & HYDRO | Denied | 1) need 2 hr @ 200 psi ( pressure dropped 5 psi in 1/2 hr due to leak at plug) 2) orange cap ( head guard) on head 3) electric room will now have a hard lid. Walls are not demising ( plans dont reflect this change) Submit as builds and now need a pendant dropped in electric room. See plans for details T16bu00843 |