Permit: T16BU00830

Parcel: 13204205B


Addresses:

2747 E AIRPORT DR


Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Permit Number - T16BU00830

Inspection Description - FIRE SPKLR - OH PIPING & HYDRO

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2016 FIRE SPKLR - OH PIPING & HYDRO Approved
06/29/2016 FIRE SPKLR - OH PIPING & HYDRO Denied Did Pass hydro ( 200 lbs for 2 hrs)
1-Must submit as builds of extra branch line installed with 5 heads
2-Must move insulation up off of uprights and where it is blocking distribution