Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2016 | FIRE SPKLR - FINAL | Approved | ||
| 07/13/2016 | FIRE SPKLR - FINAL | Denied | 1) need add head for coverage SE corner of building per marked plans 2) head taped 3) need to raise head for coverage over duct work 4) taped head 5) room has two heads that are 15 feet off the East wall 6) Insulation too low and touching a few uprights |