Permit: T16BU00733

Parcel: 10922005H


Addresses:

3570 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
05/24/2016 FIRE SPKLR - OH PIPING & HYDRO Approved
05/23/2016 FIRE SPKLR - OH PIPING & HYDRO Partial Approval PARTIAL APPROVAL
Passed hydro 200 lb for 2 hours.
Need to have ceiling tiles removed over dining area and serving area to visualize uprights and coverage.
Need to visualize uprights over bathroom hard lid.