Inspection History: FIRE - ALARM FINAL

Permit Number - T16BU00625

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/07/2017 FIRE - ALARM FINAL Approved
02/27/2017 FIRE - ALARM FINAL Denied 1) Add two notification devices to Bldg 6 second floor northwest offices.
2) Add one strobe only Bldg 6 second floor bath/rehab room
3) Remote annunciators need to operate properly
4) Labels in all the building need to be corrected to reflect room numbers
5) Each building must go into alarm individually not all in alarm
02/24/2017 FIRE - ALARM FINAL Partial Approval Swap two strobe only in the kitchen with two horn strobes. Need to move Av's to 80" to bottom of lense. Dome lights in Lt-2 and St-6 need to be tested. Also do 10% of the complete fire alarm system
02/17/2017 FIRE - ALARM FINAL Partial Approval 1. All initiating devices have been tested and passed.
2. Waiting for new dome light.
3. Ok for TCO.
02/16/2017 FIRE - ALARM FINAL Partial Approval Tested the first floor and second floor east only. Tested water flow, tamper, ansul system and nurse call. Notification devices need to be 80" to bottom of lense per drawings. Lt-2 and ST-6 dome light did not operate properly