Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16BU00625
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2017 | FIRE - ALARM FINAL | Approved | ||
| 02/27/2017 | FIRE - ALARM FINAL | Denied | 1) Add two notification devices to Bldg 6 second floor northwest offices. 2) Add one strobe only Bldg 6 second floor bath/rehab room 3) Remote annunciators need to operate properly 4) Labels in all the building need to be corrected to reflect room numbers 5) Each building must go into alarm individually not all in alarm |
|
| 02/24/2017 | FIRE - ALARM FINAL | Partial Approval | Swap two strobe only in the kitchen with two horn strobes. Need to move Av's to 80" to bottom of lense. Dome lights in Lt-2 and St-6 need to be tested. Also do 10% of the complete fire alarm system | |
| 02/17/2017 | FIRE - ALARM FINAL | Partial Approval | 1. All initiating devices have been tested and passed. 2. Waiting for new dome light. 3. Ok for TCO. |
|
| 02/16/2017 | FIRE - ALARM FINAL | Partial Approval | Tested the first floor and second floor east only. Tested water flow, tamper, ansul system and nurse call. Notification devices need to be 80" to bottom of lense per drawings. Lt-2 and ST-6 dome light did not operate properly |