Permit: T16BU00587

Parcel: 11713177A


Addresses:

201 S STONE AV

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
05/03/2016 FIRE SPKLR - UG, PIPING, HYDRO Approved hydro passed - 200 psi when read. Pressured up at 6 am, read at 840 am. May bury line. Still needs flush
05/02/2016 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval pipe only approval. Thrust blocked, joints wrapped, tracer wire in place, just need pressure test over 2 hours without pressure loss.
04/27/2016 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval still laying more pipe. current pipe is approved.