Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T16BU00537
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/06/2017 | FIRE - ALARM FINAL | Approved | ||
11/30/2016 | FIRE - ALARM FINAL | Partial Approval | 1. Tested all duct detectors. All verified. 2. Tested 3 Kitchen Hoods. All verified. 3. Need to verify panic delay once installed. 4. Waiting for As Built drawing from Climatec. |
|
11/14/2016 | FIRE - ALARM FINAL | Partial Approval | Need to test the kitchen ansul systems. Tested via the microswitch. Need to test the duct smoke detectors for proper shut down. Need to test the ground fault monitoring. Request AsBuilt drawings from Climatec. Need to verify the panic delay once it is installed. Verified monitoring via cellular unit. Water flow and tamper ditinct signals. Tamper switches verified. Manual pull station verified. Smoke's above the panels verified. |