Inspection History Details
Inspection Status: Closed
Inspection History: FIRE - ALARM FINAL
Permit Number - T16BU00477
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Closed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/12/2022 | FIRE - ALARM FINAL | Closed | PERMIT CLOSED CONTRACTOR DID NOT CALL IN INSPECTION. | |
06/03/2016 | FIRE - ALARM FINAL | Denied | Plans and sign state there is a 15 sec delay 1) two doors are 25 and 28 sec 2) voice notification not operating |