Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG PIPING FLUSH
Permit Number - T16BU00390
Inspection Description - FIRE SPKLR - UG PIPING FLUSH
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2016 | FIRE SPKLR - UG PIPING FLUSH | Approved | was flushed on 4/28/16. no flush needed since connection was broke at base of riser AFF to pressure test both underground and the overhead seperately. OK to reconnect with out a reflush ( no debris around to penetrate pipe). | |
| 04/28/2016 | FIRE SPKLR - UG PIPING FLUSH | Denied | NO PRESSURE TEST PERFORMED/INSPECTION OF JOINTSJ, MUST DIG UP |