Permit: T16BU00256

Parcel: 133165760


Addresses:

2040 N WILMOT RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
03/29/2016 FIRE SPKLR - UG, PIPING, HYDRO Approved Hydro approved. Still need to flush both lines. Still need to change FDC's. See #4 in previous inspection.
02/25/2016 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval 1) Still needs hydro on both lines.
2) Still needs flush on both lines.
3) OK to bury both lines.
4) Need to change manifold/siamese FDC's. Currently stamped with "standpipe" lettering. Need to be stamped with "auto spkr" lettering.
02/19/2016 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval 1) UG approved on main fire line. Still needs hydro. Ok to backfill.
2) UG/hydro still needed on remote FDC section. Not yet installed.