Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | ||
04/25/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Denied | Pressure test only - pressure when read was between 190 and 195 Lbs. Contractor states that it was pressured all weekend. They will drain it, pressure it up tomorrow around 530 am and call in another inspection for it for tomorrow. | |
04/21/2016 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | 1. Partial for piping visual. Ok to backfill. Still need hydro. |