Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2016 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | 1) Nozzle over fryer needs to be 30-55" This may require all nozzles to be moved. Waiting on reply from captiveaire. 2) Push button too close, 9', however we will approve. Nigel will not be approved in the future if push/pull is not 10'-20' from hood. 3) Operating pressure was initially too high, 75 psi. Cannot be over 70. After nozzle cleaning it dropped to 70. 4) Need to submit as builts. They need to reflect actual setup. Appliances, pull station, etc... 5) Submit actual calcs. We need all numbers. Pipe length, # of couplings, psi, gpm, vertical rise, etc... 6) Appliances need to shut off when hood loses power. 7) Not approved to cook. If any changes to pipe size, etc... are required, we will need to conduct another acceptance test. |