Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2016 | FIRE SPKLR - FINAL | Approved | ||
| 06/30/2016 | FIRE SPKLR - FINAL | Partial Approval | Flow switch - 30 sec on both risers - pass 2 " main drain passed pressure on both mains at 68-70 psi on flow for 1 minute Still Need to- secure insulation from falling into uprights Drop pendants in open wherehouse on West line so they are below the bottom of the lowest chord on the wood truss ( truss is blocking) |