Permit: T16BU00071

Parcel: 10707014B

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T16BU00071

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/01/2016 FIRE SPKLR - FINAL Approved
06/30/2016 FIRE SPKLR - FINAL Partial Approval Flow switch - 30 sec on both risers - pass
2 " main drain passed pressure on both mains at 68-70 psi on flow for 1 minute
Still Need to- secure insulation from falling into uprights
Drop pendants in open wherehouse on West line so they are below the bottom of the lowest chord on the wood truss ( truss is blocking)