Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2016 | FIRE SPKLR - FINAL | Approved | ||
| 03/22/2016 | FIRE SPKLR - FINAL | Denied | 1) Replace 2 painted heads (bathroom and closet). 2) Add lockout to fire bell breaker. 3) 2 heads in kitchen obstructed by soffit. Three options. -Move heads back to 10' off wall and provide new calcs. -Drop heads. 1-12" from ceiling. Max 1" obstruction from bottom of deflector to bottom of soffit. -Add sidewalls or pendents under soffit. |