Permit: T16BU00030

Parcel: 134031450

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
01/14/2016 FIRE SPKLR - UG, PIPING, HYDRO Approved Piped as per plans : Tapped into an existing 3 inch main in the club house, routed over to the East side and dropped down with CPVC to copper connection. CPVP coming off off copper from building.
passed hydro - 200 lbs for 2 hrs ( pumped up at 7 am , read at 9:15 am). trench is more than 36 inches.