Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
Permit Number - T15OT01675
Inspection Description - SIGN ELECTRIC
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/03/2016 | SIGN ELECTRIC | Denied | THERE IS NOT A DESIGNATED TIMER AND CIRCUIT. SIGN APPEARS TO RUN OFF THE PARKING LOT LIGHTING CIRCUIT. ALL OF THE SIGNS LOCATED ON THIS BUILDING APPEAR TO RUN OFF THE LIGHTING CIRCUIT, FUTURE CHANGES MAY NEED TO BE MADE TO INCLUDE INDIVIDUAL CIRCUITS AND TIMERS. |