Permit: T15OT00877

Parcel: 137276530


Addresses:

1600 W VALENCIA RD


Inspection Status: Approved

Inspection History: SIGN SITE REVIEW

Permit Number - T15OT00877

Inspection Description - SIGN SITE REVIEW

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2015 SIGN SITE REVIEW Approved PERMIT READY TO PAY FOR & PICK UP
08/07/2015 SIGN SITE REVIEW Correction Required PANDA EXPRESS
T15OT00877
REVSION: #1
RECEIVED: 8/3/15
REVIEWED: 8/6/15 by BWiese
APPLICATION & DRAWING: correction required. A revision is required as per Sign Code 3-16.
1.Drawings: Information required on drawings include.
a.SIGN(A) : DISCONNECT SWITCH must be labeled on elec details.
b.SIGN(B) : DISCONNECT SWITCH must be labeled on elec details.
c.SIGN(C) : DISCONNECT SWITCH must be labeled on elec details.
d.SIGN(D) : DISCONNECT SWITCH must be labeled on elec details.
e.SIGN(E) : the square footage in "decimal feet" to match application.
f.SIGN(F) :
1. the square footage in "decimal feet" to match application.
2. Electrical details and DISCONNECT SWITCH
g. SIGN(G):
1.the square footage in "decimal feet" to match application.
2.The caisson and its width & length in "decimal feet"
3.OAH from the Top of Curb.
4.A construction/electrical diagram of SIGN (G) showing
a.Construction details
b.Attachment details (number, size and type of anchors/bolts)
c.Type of illumination (ex. LED)
d.Show & indicate the DISCONNECT SWITCH
e.Indicate the AMPS__ VOLTS__ CIRCUITS__
5.Engineering required for footings, as cabinet & pole cover combined exceed 60 sq ft.
h.SIGN(H): all corrections same as for SIGN(G):

SITE PLAN:
1.45 degree angle at corner is in wrong location (see brian)
2.Both COT stamped site plans show existing signs on site. There must be call outs indicating that these existing sign will be removed (on the application and the site plan).
3.Both street frontage measurements must be illustrated on the site plan.
4.Premise needs to be identified as a "STAND ALONE PREMISE"
07/21/2015 SIGN SITE REVIEW Denied PANDA EXPRESS
T15OT00877
REVSION: NA/ORGINAL
RECEIVED: 7/2/15
REVIEWED: 7/21/15 by BWiese
APPLICATION & DRAWING DENIED. A revision is required as per Sign Code 3-16.
Some of the revisions required include but are not limited to
1. Drawings:
a. Drawings must be laid out in the format required by the COT. (see attached PDF)
b. Remove page 5 from the submittal, (There are no signs on this elevation)
c. Each and every sign must have its own letter to match the application.(even if identical to another sign)
d. Each and every sign must have its own page.(even if identical to another sign) Ex. Page One is SIGN (A), Page Two is SIGN(B) etc.
e. On every page, Elevations must be labeled with the direction they face. EX "North Elevation"
f. On every page, Electrical details must include the following statement
"24 HOUR programmable timer installed to comply with the COT outdoor lighting code"
g. On every page, Electrical details must clearly indicate AMPS, VOLTS & CIRCUITS
h. On every page, Electrical details must clearly show and label the disconnect switch.
i. On every page, All sign measurements must be indicated in "Feet. Decimal" not "feet.inches"
j. On every page,: Measurements on drawings must match the measurements on the application.
k. On every page,: The OAH "overall height" of sign must shown on the elevation to match the application.
l. Color palette is superfluous information.
m. Remove speaker cabinets and clearance bars from the submittal
n. Menu board drawing requires dimensions for the OAH, the illuminated cabinets overall width & length.
o. Freestanding signs drawings ie: Monument & Menu must be laid out in the format required by the COT. (see attached PDF)
p. Site plan for the Monument sign requires a very specific format required by the COT. (see attached PDF)
q. Site plan for the Monument sign must be drawn on the Development Plan drawing that is stamped and approved by the City of Tucson Plan Review desk.