Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SITE REVIEW
Permit Number - T15OT00859
Inspection Description - SIGN SITE REVIEW
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/20/2015 | SIGN SITE REVIEW | Approved | PERMIT READY FOR PAYMENT AND PICK UP | |
07/06/2015 | SIGN SITE REVIEW | Denied | CHAPMAN HONDA T15OT00859 REVSION: NA/ORGINAL RECEIVED: 6/29/15 REVIEWED: 7/6/15 by BWiese APPLICATION & DRAWING DENIED. A revision is required as per Sign Code 3-16. Some of the revisions required include but are not limited to 1. Drawings: a. Drawings have not been laid out in the format required by the COT. b. Pages need to be numbered. EX. "Page 1 of 9" etc c. Page One should only reference Sign (A) d. Page Two should only reference Sign (B) etc e. All sign measurements must be indicated in "Feet. Decimal" not "feet.inches" f. Drawings must indicate what scale they are drawn to for 11 x17 paper g. Measurements on drawings must match the measurements on the application. h. "Over all Height" OAH of Signs are not indicated on the drawing of the building frontage. i. Square Footage is not indicated on the drawings. j. Electrical details do not clearly indicate a "Disconnect switch" k. Electrical details do not include the following statement "24 HOUR programmable timer installed to comply with the COT outdoor lighting code" l. Electrical details do not clearly indicate AMPS, VOLTS & CIRCUITS 2. Location Map: a. Adjacent road on the east of parcel is not labeled |