Permit: T15OT00337

Parcel: 13621004E

Inspection Status: Approved

Inspection History: SIGN SITE REVIEW

Permit Number - T15OT00337

Inspection Description - SIGN SITE REVIEW

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2015 SIGN SITE REVIEW Approved EMC COPY CAN NOT CHANGE MORE THAN ONCE PER HOUR / CAN NOT BE ANIMATED & OVER 200 NITE-TIME NIT'S
03/31/2015 SIGN SITE REVIEW Correction Required Comments from Dan Santa Cruz....Upon electrical review of the new monument sign project at 7500 E. Golf links Rd, the following deficiencies where found:
#1. In order to ensure a safe and code compliant electrical installation, please provide the following information in the plan submittal.
(a).An electrical site plan showing wiring methods such as, conduit, branch circuit conductors types and sizes, overcurrent protection, circuit #, panelboard designation and location, disconnecting means and location, time clock or photocell control, grounding and bonding. Ref. NEC art. 250, 300, 310, 408.4, 600.
(b) Listing information as required per NEC 600.3.
(c). Full compliance with Chapter 5 of the Tucson Outdoor Lighting Code.
Dan Santa Cruz
Electrical Plans Examiner
More requirements from Brian Wiese are as follows: the drawing must indicate that the OAH of sign is measured from the top of curb on Golf Links.