| 04/09/2015 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/07/2015 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/07/2015 | ELECTRIC - FINAL | Denied | 1. MORE THAN 3 WIRES IN ONE PIPE 2. #6 AND SMALLER TO BE COLLAR OF INSULATION 3. NEUTRAL IN J-BOX TO BE TAPED 4. #6 WIRES IN J-BOX AND SERVICE PANEL TO BE CAPPED-OFF 5. J-BOX TO BE BONDED |
|
| 03/18/2015 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |