12/26/2015 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CALL OUT BY TFD: ADDRESS ON SITE IS 2332 BUT ONLINE WITH PC ITS 2336 E MONTEREY VISTA
THE TENANT STATES THAT ALL POWER WAS OFF LAST NIGHT AND EARLY THIS MORNING THE OWNER CAME OVER AND FIXED THE PROBLEM, LATER THAT MORNING THE POWER WENT OFF AGAIN AND SHE CALLED THE FIRE DEPT. I ARRIVED ONSITE AND ALL POWER TO THE DWELLING UNIT WAS OFF. ALL THE CIRCUIT BREAKERS TO THE INTERIOR SUB PANEL WERE ON, I CHECKED THE MAIN SERVICE AND ALSO IN THE ON POSITION THE DISCONNECT HAS TWO 30 AMP FUSES.

THE INTERIOR SUB PANEL LOCATED IN THE UTILITY ROOM WAS REPLACED AND A ADDITIONAL CIRCUIT WAS ADD, ALL WITHOUT PERMITS. THE SERVICE IS FOR 30 AMPS YEP THERE IS ONE CIRCUIT THAT IS FOR A DRYER OF 30 AMPS.. THE MAIN GAS FURNACE IS TAGGED BY SOUTHWEST ON JULY OF 2014 UNSAFE TO OPERATE.
THE TENANT IS USING THREE POTABLE SPACE HEATERS AS PERMANENT HEATING, THE CIRCUITS ARE BEING OVER LOADED.

THE DWELLING UNIT WAS CONDEMNED FOR UNPERMITTED WORK, CIRCUITS BEING OVERLOADED, NO PERMANENT HEATING AND THE STATEMENT MADE FROM THE TENANT THAT SHE SMELLED SOMETHING BURNING THEN THE POWER WENT OFF. THE TENANT ALSO STATED THAT SHE WENT THROUGH THIS LAST WINTER. ALSO STATEMENTS MADE FROM THE OWNER.. ALL DOCS AND PICS IN SIRE.
SCHEDULE A 30 DAYS FOLLOW UP INSPECTION..