Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2015 | INSP - INITIAL CODE ENFORCMENT | Approved | VISITED SITE, TFD HAD CLEARED THE SCENE UPON ARRIVAL, MET WITH TFD CAPTAIN WHO STATED THE FIRE STARTED IN THE BATHROOM AND CAUSED BY THE OLD BATHROOM FAN AND BAD WIRING. MY FINDINGS ARE AS FOLLOWS: >APPEARS FIRE STARTED WHERE THE WIRING CONNECTED TO THE FAN EVIDENCED BY HEAVY TAPE AT THE END OF BURNED WIRES. > TWO 2 X 6 RAFTERS ON EITHER SIDE OF THE FAN HEAVILY BURNED. > 4 FT X 4 FT SECTION OF 1" X 8" TONGUE AND GROOVE ROOF SHEATHING DAMAGED. > 5 FT X 8 FT DRYWALL CEILING DAMAGED IN THE BATHROOM. CHECKED AND FOUND SERVICE HAD BEEN TURNED OFF AT THE MAIN SERVICE PANEL BY TFD. TFD INFORMED OCCUPANT AND DAUGHTER OF THE OWNER WHO LIVES AT 5328 NOT TO TURN POWER BACK ON UNTIL ALL ISSUES HAVE BEEN ADDRESSED. ** S/W GAS RAN A LINE TEST, EVERYTHING DID CHECK OUT OK. HE DID NOT RELIGHT THE HOTWATER HEATER DUE TO NOT HAVING FLUE VENT/ TERMINATION CAP. THE STOVE WAS LIT AND GAS DID REMAIN ON. TENNANT TREAVOR HARKINS IS A FAMILY FRIEND OF THE OWNER AND WILL BE STAYING WITH THE OWNER OF THE PROPERTY, TWO HOUSES DOWN. EMERGENCY NOV TO VACATE WAS ISSUED TO THE OCCUPANT AND DID INCLUDE PERMITS REQUIRED FOR ALL REPAIRS. NOV WAS ISSUED AND SIGNED FOR BY TENANT TREAVOR HARKINS. |