Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date |
Description |
Inspector |
Results |
Comments |
| 10/07/2015 |
INSP - INITIAL CODE ENFORCMENT |
|
Approved |
Complaint residential fire alarm 21567 561.. Arrived on site to find fire captains on site along with fire investigators ..fire started in a rear shed attached to the block structure appears to be done without a permit. Tenant had installed solar panels throughout the rear roofline of home. All lines were run through the attached shed at the rear where batteries and inverters are being supplied for the solar unit. Fire was put out by aTFD and TEP shut power at the meter .. however they are still getting a load from the solar panels going into the damaged shed and damaged electrical system... system wires were cut and terminated with wire nuts by the tenant of the unit at the roof level.... Thus terminating the solar panels.. no gas to unit for the last 14 years, each room was supplied with propane heaters in both bedrooms, stove in kitchen also supplied with propane unacceptable use .. no smoke detectors in or leading to bedrooms ..roof system at some point in time was elevated evident by electrical drop now tucked under roofline and weathered osb .. notice and order to vacate as well as the indemnity notice was signed by the tenant... Property was posted and phone contact was made to the property owner with meeting set |