Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date |
Description |
Inspector |
Results |
Comments |
| 06/30/2015 |
INSP - INITIAL CODE ENFORCMENT |
|
Approved |
UPON ARRIVAL OF THE SITE, I FOUND TFD HAD CLEARED THE SCENE. MET WITH TRAILER OWNER ANNA PEDROZA WHO STATED TFD WENT UP ON THE ROOF, UNPLUGGED THE COOLER MOTOR AND THEN SHUT POWER OFF AT THE PEDESTAL. I CHECKED THE COOLER, THE COOLER MOTOR SMELLED LIKE IT HAD BURNED OUT. THE COOLER PAD WAS IN BAD CONDITION BUT THE PUMP HAD BEEN REPLACED. I TURNED POWER BACK ON AT THE PEDESTAL AND THEN ISOLATED THE BREAKER THAT RAN THE COOLER. THE SUB PANEL WAS NOT MARKED AND AS I CHECKED THE POWER I MARKED THE PANEL AS I WENT. COOLER WAS LEFT OFF. I ALSO FOUND PANEL HAD NO COVER PLATE AND ALSO FOUND A LIGHT MISSING IN THE HALL WAY. NOV WAS ISSUED FOR THE COOLER AND ELECTRICAL ISSUES. |