Case: T15DV00038

Parcel: 13005053A


Addresses:

1930 S NORRIS AV

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
01/12/2015 INSP - INITIAL CODE ENFORCMENT Approved THERE IS AN ELECTRIC TYPE OF FURNACE WHICH HAS BEEN INSTALLED IN THE INTERIOR SPACE OF A HALLWAY CLOSET. THE UNIT'S HOUSING IS MISSING AND IS INOPERABLE. THE RETURN AIR IS MOUNTED ON THE INTERIOR DOOR OF THE CLOSET. THE UNIT IS UNSAFE AND HAS EXPOSED WIRING IN THE INTERIOR OF THE CLOSET. THE UNIT WAS INSTALLED WITHOUT A PERMIT AND NOT IN ACCORDANCE WITH THE MANUFACTURES INSTRUCTIONS. THE CLOSET AREA SERVES AS A FURNACE ENCLOSURE AND A CLOSET.

THE MAIN DISCONNECT HAS ELECTRICAL DEFECTS, THERE IS MULTIPLE CONDUCTORS ON A LUG, NO LABELING, CIRCUIT BREAKER IS TRIPPING WHEN THE DRYER IS TURNED ON, EXTERIOR 4 GANG BOX HAS UNUSED OPENINGS, THERE IS MISUSE OF EXTENSION CORDS, RECEPTACLES IN THE BEDROOM ARE INOPERABLE.