Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2016 | FIRE - ALARM FINAL | Approved | approved. keeping simplex permit open, waiting on as builts. | |
| 09/21/2016 | FIRE - ALARM FINAL | Denied | 1) Still need to test north waterflow/tamper. 2) Still need to test 3 smokes south corridor. 3) Need to test door drops. 4) Repair strobe in bathroom #3902 5) Need a clean panel. Showing trouble and ground faults. |