Permit: T15CM08596

Parcel: 12710178C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T15CM08596

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/16/2016 ELECTRIC - INTERMEDIATE Approved
03/14/2016 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :23No Description.| 99946
*
03/09/2016 ELECTRIC - INTERMEDIATE Denied 1 COPPER AND ALUM. CONDUCTORS NOT TO BE SPLICED WITHOUT APPROVED CONNECTORS - 110.14 NEC.
2 ALUM. GROUNDING CONDUCTOR TO BE TERMINATED AT THE CONNECTOR FOR HCF (MC). ONLY COPPER GROUNDING CONDUCTOR MAY TERMINATE ON METAL ENCLOSURE AND DEVICE PER LISTING.
3 MC SHALL BE TERMINATED USING LISTED, APPROVED CONNECTORS. NEC 110.3
4 CABLE FOR BRANCH CIRCUITS IN PATIENT CARE EXAM ROOM CIRCUITS SHALL BE COMPLETE RUNS TO PANEL OR MAINTAIN GROUNDING REQUIREMENTS OF 517.13
03/03/2016 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/04/2016 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/02/2016 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/26/2016 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*