Permit: T15CM08111

Parcel: 136254110

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
08/25/2016 FIRE SPKLR - UG, PIPING, HYDRO Approved
08/16/2016 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval
08/12/2016 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval These are notes from NS:
PARTIAL APPROVAL
All C900 pipe and tracer tha is already in place with thrust blocks may be back filled.
An c 900 still to be laid ( on the East permimeter) may be back filled if no thrust block is need.
Still needs 200 lb test
08/12/2016 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Following up on NS inspection. East end approved. OK to backfill. 3stubups and thrust blocks. Still need to visualize remaining stubups and thurst blocks for risers only.
08/09/2016 FIRE SPKLR - UG, PIPING, HYDRO Denied cancelled. not ready.
07/26/2016 FIRE SPKLR - UG, PIPING, HYDRO Denied 1. Need to pull separate underground permit.