Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T15CM07917
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/08/2016 | FIRE - ALARM FINAL | Approved | ||
11/02/2016 | FIRE - ALARM FINAL | Partial Approval | Waiting on intelligibility report from redhawk. | |
10/28/2016 | FIRE - ALARM FINAL | Partial Approval | Install head in "party room" finish installing the ceiling tiles add coverage to storage room # 106 FDC Caps need to be in place Taped head in the stairwell needs to be corrected. Escutcheons, plastic clips and plastic caps need to be added/removed Theater 12,13 & 14 projectors were not operating and or did not shut down with the fire alarm system. Lights did not turn on with alarm in the theater rooms Need to provide proof of the inteligability test for the fire alarm system. Function test of the Ansul system needs to be scheduled Address needs to be installed on the building Provide the key for KNOX box Provide the monitoring paperwork Need to test the emergency and exit lights. |
|
10/25/2016 | FIRE - ALARM FINAL | Partial Approval | Check the audibility and intelligibility of the voice evac speakers. Provide documentation showing meets the minimum code requirements. Smoke detector above the RAAN - provide documentation regarding the reflective ceiling plan and proper spacing. Provide monitoring station UL and or FM certificate. manually verified the flow switch due to the water not being turned on. Need to verify with fire sprinkler final. Phone line 2 is showing a comm fail, check the long distance on phone line Provide documentation from central station for signals received. All speakers, speaker strobes and strobes to be mounted at a minimum 80" to the bottom of the lens...locations to be corrected. Theater 5 South corridor exit South corridor bathroom Outside theater 7 Stage room south corner back exit womens bathroom south mens bathroom south Side by 7 Starcade Foyer Box office x 2 Extreme digital x 2 Theater 14 front Managers office x 2 North corridor x 2 Mens bathroom north Womens bathroom north Theater 10 by door Connect the ansul system with the fire alarm Need to verify the shout down of projectors. |