Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T15CM07917

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2016 FIRE - ALARM FINAL Approved
11/02/2016 FIRE - ALARM FINAL Partial Approval Waiting on intelligibility report from redhawk.
10/28/2016 FIRE - ALARM FINAL Partial Approval Install head in "party room"
finish installing the ceiling tiles
add coverage to storage room # 106
FDC Caps need to be in place
Taped head in the stairwell needs to be corrected.
Escutcheons, plastic clips and plastic caps need to be added/removed
Theater 12,13 & 14 projectors were not operating and or did not shut down with the fire alarm system.
Lights did not turn on with alarm in the theater rooms
Need to provide proof of the inteligability test for the fire alarm system.
Function test of the Ansul system needs to be scheduled
Address needs to be installed on the building
Provide the key for KNOX box
Provide the monitoring paperwork
Need to test the emergency and exit lights.
10/25/2016 FIRE - ALARM FINAL Partial Approval Check the audibility and intelligibility of the voice evac speakers. Provide documentation showing meets the minimum code requirements.

Smoke detector above the RAAN - provide documentation regarding the reflective ceiling plan and proper spacing.

Provide monitoring station UL and or FM certificate.

manually verified the flow switch due to the water not being turned on. Need to verify with fire sprinkler final.

Phone line 2 is showing a comm fail, check the long distance on phone line

Provide documentation from central station for signals received.

All speakers, speaker strobes and strobes to be mounted at a minimum 80" to the bottom of the lens...locations to be corrected.

Theater 5

South corridor exit

South corridor bathroom

Outside theater 7

Stage room south corner back exit

womens bathroom south

mens bathroom south

Side by 7

Starcade

Foyer

Box office x 2

Extreme digital x 2

Theater 14 front

Managers office x 2

North corridor x 2

Mens bathroom north

Womens bathroom north

Theater 10 by door

Connect the ansul system with the fire alarm

Need to verify the shout down of projectors.