Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2018 | FRAMING | Approved | SHEATHING ON EAST WALL NAILING COMPLETE. aLL OTHER FRAMING INSPECTED PREVIOUSLY | |
| 01/30/2018 | FRAMING | Partial Approval | OKAY TO COVER UN-SHEATHED WALL. | |
| 01/18/2018 | FRAMING | Partial Approval | DOUBLE TOP PLATES ARE REQUIRED TO OVERLAP INTERSECTING WALLS. AMEND OR ATTACH WITH MECHANICAL MEANS . (hurricane ties or metal straps) ANCHOR BOLTS ARE MISSING NUTS AND WASHERS BLOCK SHEATHING SEAMS TO ACHIEVE THE APPROPRIATE NAILING PATTER OF 6 INCHES ON ALL EDGES AND 12 INCHES IN THE FEILD. |