Permit: T15CM07294

Parcel: 13323190A


Addresses:

7798 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
12/04/2015 FIRE - FINAL Approved wood racks removed from walls.
12/03/2015 FIRE - FINAL Denied 1. front & rear exit sign back up lighting and emergencyl lighting must come on when power is turned off.
2. Section 804.1 Interior trim shall be less than 10 % of the wall it is covering and must meet a Class C flame spread and smoke -developed indices when tested in accordance with ASTM E 84 or UL 723.
3. place a sign over the main exit that states " This door is to remain unlocked while the building is occupied.