Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T15CM07108
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2016 | FIRE - FINAL | Approved | ||
11/23/2015 | FIRE - FINAL | Denied | 1. Need to correct upright sprinkler coverage in offices rear of building both right and left, pocket areas because of beam. 2. Need to have approved plans approved first and then called in for an inspection and then closed out permit before calling in for sprinkler finals on your T15CM07108 permit. (Sprinkler permit in process T15BU01335) 3. Need (3) fire extinguishers 1 for every 1500 sq. feet of building and the travel distance cannot be more than 75' feet travel, type 2A-10BC. Mount min 4" inches max 3.5' feet above floor measuring to the top of the fire extinguisher. 4. Need suite numbers post on the door and rear door. |