Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 04/08/2016 |
ELECTRIC - UNDERGROUND |
|
Approved |
MEDIUM VOLTAGE DUCT BANK (8 @ 5"} FROM TEP VAULT TO EXISTING MANHOLE (NORTH); REBAR ADJUSTMENT TO TAKE CAGE BARS OFF THE GROUND. |
| 04/04/2016 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
6-6" CONDUITS EXITING TEP VAULT FIRST 40 FEET OK TO COVER. |
| 04/01/2016 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
2 - 4" COMMUNICATIONS CONDUITS OK TO COVER FROM NORTH END TO 160' SOUTH. |
| 03/01/2016 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection :* |
| 02/29/2016 |
ELECTRIC - UNDERGROUND |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 02/18/2016 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection :* |
| 02/04/2016 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
3/4" CONDUIT LATERAL LINES AT NORTH SIDE OF BLDG OK TO COVER |
| 02/02/2016 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection :* |