Permit: T15CM06746

Parcel: 13316033H

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T15CM06746

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/27/2016 FIRE - FINAL Approved Outstanding fire code items will be corrected within 30 days
01/26/2016 FIRE - FINAL Denied 1) Replace missing ceiling tile in copy room.
2) Label copy room door "FACP"
3) All exposed wires need cover plates. Open junction boxes throughout including copy room, next to inspectors test, east hallway, etc...
4) Label riser room door "riser room"
5) Need "FDC" sign mounted above fire dept. connections on west side of building.
6) Need address numbers on building. Minimum 12"
01/20/2016 FIRE - FINAL Denied Need permits for sprinkler monitoring system.
Must remove ALL remaining existing fire alarm devices.
01/11/2016 FIRE - FINAL Denied DENIED
1. MUST COMPLETE FIRE SPRINKLER FINAL AND PASS
2. NEED FIRE EXTINGUISHERS WITHIN 75 FT OF EVERY POINT IN THE BUILDING
3. SHADE COVERING THE NW EXIT DOOR IS OBSTRUCTING/OBSCURING A REQUIRED EXIT - REMOVE

PER IFC 1104.5 - EMERGENCY LIGHTING IS NOT REQUIRED