Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
10/14/2015 ELECTRIC - RECONNECT Approved
09/22/2015 ELECTRIC - RECONNECT Denied 1. INSTALL PROPER KNOCKOUT BLANKS IN MAIN PANEL DEAD FRONT.
2. OPEN PATIO J BOX FEEDING POOL EQUIPMENT.
3. SMOKE DETECTORS IN 2 NORTH BEDROOMS ARE TOO LOW.
4. UPPER RIGHT 20 AMP BREAKER, IN SUB-PANEL, IS TOO BIG FOR THE #14 WIRE.
5. ALL 3 PRONG OUTLETS, ON THE 2 WIRE SYSTEM, MUST BE CHANGED BACK TO 2 PRONG OUTLETS OR GFI'S MARKED UNGROUNDED.