Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2015 | ELECTRIC - RECONNECT | Approved | ||
| 09/22/2015 | ELECTRIC - RECONNECT | Denied | 1. INSTALL PROPER KNOCKOUT BLANKS IN MAIN PANEL DEAD FRONT. 2. OPEN PATIO J BOX FEEDING POOL EQUIPMENT. 3. SMOKE DETECTORS IN 2 NORTH BEDROOMS ARE TOO LOW. 4. UPPER RIGHT 20 AMP BREAKER, IN SUB-PANEL, IS TOO BIG FOR THE #14 WIRE. 5. ALL 3 PRONG OUTLETS, ON THE 2 WIRE SYSTEM, MUST BE CHANGED BACK TO 2 PRONG OUTLETS OR GFI'S MARKED UNGROUNDED. |