Permit: T15CM06456

Parcel: 11711076A


Addresses:

126 E ALAMEDA ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T15CM06456

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/06/2017 ELECTRIC - INTERMEDIATE Approved
08/01/2017 ELECTRIC - INTERMEDIATE Partial Approval PANELS, SWITCH GEAR, TRANSFER SWITCHES: SEF-A; UA1; SWITCH ATS; G8; SWG (TD-1); SWGR-A; TA1; MA1 4 EACH 800 AMP BREAKERS.
06/01/2017 ELECTRIC - INTERMEDIATE Partial Approval NINE PANELS INSPECTED - NEED TO MIGRATE FEEDERS IN FROM EXISTING PANELS: PANELS: P-LMA-BB3, P-LMA-GBE; P-LMA-GM2, P-LMA-1B3, P-LMA-1M2, P-LMB-2B3, P-LMB-3B4, P-LMB-3M3, L-LMP-4B4
03/28/2017 ELECTRIC - INTERMEDIATE Partial Approval PANELS PDSC, ACPBD-REFEED AND REPLACE BREAKERS.
CHILLERS CCC-AB, MCC-2 RE-FEED TO SOURCE.
02/16/2017 ELECTRIC - INTERMEDIATE Partial Approval PANEL #1 P-LHB-GG10; TRANSFER SWITCHES: #1 ATS-HSB1-GK8; #2 ATS-HSB1-GK8. OK TO ENERGIZE EQUIPMENT.
02/08/2017 ELECTRIC - INTERMEDIATE Partial Approval SWICHE GEAR B PARTIAL
SES B ATS B, NEEDS TO REMOVE TEMP POWER AND INSTALL EMERGENCY BACK UP POWER
11/29/2016 ELECTRIC - INTERMEDIATE Partial Approval GROUND CABLE TO OFFICE #1 CAD WELDED TO MAIN GROUNDING SYSTEM. OK TO COVER PROGRESS AREA.
09/13/2016 ELECTRIC - INTERMEDIATE Partial Approval OKAY TO CLOSE AND ENERGISE PENDING 3RD PARTY TORQUE REPORTS.HMB1-GJ8, HMA1-GJ9, HHB1-GK8, AND HHA1-GK9.
08/16/2016 ELECTRIC - INTERMEDIATE Partial Approval OKAY TO CLOSE SWTICH GEAR SECTIONS "HDB1-3D1" AND "HDA1-3E1", 3RD PARTY HAS TORQUE RESULTS, FINAL CONNECTIONS NOT EXPECTED TO BE INSPECTED FOR 3-4 WEEKS, HI-POT TESTS WILL BE EMAILED TO ME.