Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2015 | ELECTRIC - FINAL | Approved | ||
| 09/15/2015 | ELECTRIC - FINAL | Denied | 1. CANNOT STACK LUG FOR GROUNDS- MAIN DISCONNECT- MULTI TAPS ALSO 2. PV GROUNDING ELECTRODE CONDUCTOR TO BE PER 250.64 E 3. PV PANEL BREAKER TO BE PER 705.12 (D 4. PV LABEL LUG TO BE PER 690.17 AND 705.12 5. TERMINATE GROUNDING ELECTRODE CONDUCTOR PV DISCONNECT AND CONTINUOUS 250.64 6. LOOSE CONDUCTOR TERMINATIONS 7. LUGS HAVE BEEN MODIFIED BY DRILLING 110.3 8. NO ROOF INSPECTION AT THIS TIME |
|
| 09/08/2015 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site: UNSURE OF SCOPE OF WORK PROVIDE FULL DESCRIPTION OF WORK NOTE: FEEDER TO SUB PANEL ON 200 AMP - PROVIDE MIN 310 CU WIRE INCOMPLETE INSPECTION |