Permit: T15CM06209

Parcel: 116040540

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/16/2015 ELECTRIC - FINAL Approved
09/15/2015 ELECTRIC - FINAL Denied 1. CANNOT STACK LUG FOR GROUNDS- MAIN DISCONNECT- MULTI TAPS ALSO
2. PV GROUNDING ELECTRODE CONDUCTOR TO BE PER 250.64 E
3. PV PANEL BREAKER TO BE PER 705.12 (D
4. PV LABEL LUG TO BE PER 690.17 AND 705.12
5. TERMINATE GROUNDING ELECTRODE CONDUCTOR PV DISCONNECT AND CONTINUOUS 250.64
6. LOOSE CONDUCTOR TERMINATIONS
7. LUGS HAVE BEEN MODIFIED BY DRILLING 110.3
8. NO ROOF INSPECTION AT THIS TIME
09/08/2015 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site:
UNSURE OF SCOPE OF WORK
PROVIDE FULL DESCRIPTION OF WORK
NOTE: FEEDER TO SUB PANEL ON 200 AMP - PROVIDE MIN 310 CU WIRE
INCOMPLETE INSPECTION