Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
02/27/2017 MECHANICAL - HOODS Approved IVRS - Inspection :*
01/03/2017 MECHANICAL - HOODS Partial Approval see biulding notes 1-3-17
11/29/2016 MECHANICAL - HOODS Partial Approval 2ND WRAP ON HOOD DUCTS
11/10/2016 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
11/10/2016 MECHANICAL - HOODS Partial Approval grease duct smoke test ok
ok for 1st layer all
10/18/2016 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
10/18/2016 MECHANICAL - HOODS Partial Approval 2 layers fire wrap on 6 duct drops ok
10/13/2016 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
10/13/2016 MECHANICAL - HOODS Partial Approval grease duct sections tested on ground ok, ok to install and 1st layer fire wrap, expose all transverse joints for continued smoke testing
10/12/2016 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
10/12/2016 MECHANICAL - HOODS Partial Approval 1 small pants and 1 6' straight leaking
10/11/2016 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
10/10/2016 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
10/10/2016 MECHANICAL - HOODS Partial Approval 4 curb drops ok on smoke test