Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T15CM06092

Parcel: 12709001F

Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T15CM06092

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2015 FIRE - FINAL Approved Emergency generator started immediately when power to building was shut down, walked building found lights on 1st and 2nd floor working along with all exit signs. Tested 2nd floor roll up gate operated using a Knox box as the operating switch.
10/26/2015 FIRE - FINAL Denied 1. Add sprinkler coverage under outside awnings to patios
2. Need to refill spare head sprinkler box
3. Need annual fire alarm inspection reports
4. Need monthly generator testing reports
5. Need to have a test run for the emergency generator making sure the following work under actual load: Exit signs, EM Lighting for hallways and stairwells, Roll up gate also need to add a switch on egress side of gate for operation if wired into EM wiring if not then gate needs to open manually when electrical power is fails. All this shall be witness by a TFD inspector both 1st and 2nd floors.
10/16/2015 FIRE - FINAL Denied 1. need fire extinguishers within 75 ft of all places
2. need sign over security gate that states, " This gate to remain open while the building is occupied"
3. need emergency lighting placed:
a) waiting room #247
b) big group room
c) hallway into phase 2 ( on contractors plans pg A2.1)
4) Need exit sign in hallway to phase 2 to work on back up lighting