Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T15CM06053
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2017 | FIRE - FINAL | Approved | ||
| 12/13/2016 | FIRE - FINAL | Partial Approval | need sensitivity report on all smoke detectors | |
| 11/21/2016 | FIRE - FINAL | Partial Approval | 1. Ok to occupy 6th floor units. 2. Tested smokes, smoke dampers, horn/strobes, door closures, smoke gaskets, etc. All good. |
|
| 11/17/2016 | FIRE - FINAL | Partial Approval | Sixth Floor, need to fill in open conduit with fire stop. The fire smoke dampers need to be labeled and tested. Need keys for elevator key box. Install smoke gaskets and door closers on rated doors throughout building where missing. Remove cover from fire sprinkler head in closet on first floor. |
|
| 10/28/2016 | FIRE - FINAL | Partial Approval | Floors 1-4 approved by CB. 5th floor approved by me (JVINCENT). TCO pending bldg approvals OK for not having a fully functional fire alarm sytem above the 5th floor. | |
| 10/26/2016 | FIRE - FINAL | Partial Approval | 1. Tested corridor smokes, horn/strobes and Fire Smoke Dampers on 3rd and 4th floors. All tested ok and reported to panel and central station. 2. Tested Heat detector and horn/strobes on 2nd floor. All Tested good. 3. Tested Elevator firefighter recall. Tested good. |
|
| 10/18/2016 | FIRE - FINAL | Partial Approval | 1. Tested interlocked smoke detectors in 5th floor units. All passed. | |
| 10/11/2016 | FIRE - FINAL | Partial Approval | 1. Tested interlocked smoke detectors in all units for 3rd and 4th floors. Everything good. | |
| 05/09/2016 | FIRE - FINAL | Partial Approval | 5TH FLOOR 4FT LIFT, | |
| 04/08/2016 | FIRE - FINAL | Partial Approval | 8ft lift on stair #2, 4ft lift on ramp north side, 12ft lift GL 4.5/f.6-g. |