Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T15CM06053
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2016 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/14/2016 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/20/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/20/2016 | PLUMBING - ABOVE CEILING | Partial Approval | 608,603,610,605,612,607 ok to rock soffits/drop cielings | |
| 10/14/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/14/2016 | PLUMBING - ABOVE CEILING | Partial Approval | 5th floor hallway ok to cover | |
| 10/05/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/16/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/24/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/24/2016 | PLUMBING - ABOVE CEILING | Partial Approval | roms 501,502,504,506,508,503,510,505,507 ok to rock except shafts and chases. | |
| 08/12/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/11/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/27/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/20/2016 | PLUMBING - ABOVE CEILING | Partial Approval | 6TH FLOOR ROOMS 602, 604, AND 606. NOTE: NEED PROPER FIRE CHAULKING THUR FLOORS AND WALLS PENETRATION AS REQUIRED. | |
| 07/13/2016 | PLUMBING - ABOVE CEILING | Partial Approval | exterior walls and party walls 5th floor ok to cover | |
| 07/11/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/11/2016 | PLUMBING - ABOVE CEILING | Partial Approval | ALL ABOVE CEILING 5TH FLOOR ONLY OK TO COVER | |
| 06/23/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/09/2016 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |