Permit: T15CM05854

Parcel: 13701007U


Addresses:

5580 S NOGALES HY


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T15CM05854

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
08/28/2015 ELECTRIC - SERVICE UPGRADE Approved PER ELEC FINAL
08/26/2015 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/26/2015 ELECTRIC - SERVICE UPGRADE Denied NOTES 4 & 5 FROM PREVIOUS. REPLACE SHARP POINT SELF-TAPPING SCREWS AND SERVICE DEADFRONT. STRAP SEAL-TIGHT. LOAD SIDE TO PANEL B FROM PANEL A
08/24/2015 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/24/2015 ELECTRIC - SERVICE UPGRADE Denied 1. LABEL DISCONNECTS
2. 3/4 K.O. SEAL MISSING AND TWO WIRES ON ONE LUG
3. BREAKER BLANKS MISSING
4. STRAP SEAL TIGHT TO UNIT
5. 1 1/2 STUB TO BE REMOVED AND SEALED
6. NEUTRAL TO BE IN PROPER SIZE LUG