Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2015 | ELECTRIC - SERVICE UPGRADE | Approved | PER ELEC FINAL | |
| 08/26/2015 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/26/2015 | ELECTRIC - SERVICE UPGRADE | Denied | NOTES 4 & 5 FROM PREVIOUS. REPLACE SHARP POINT SELF-TAPPING SCREWS AND SERVICE DEADFRONT. STRAP SEAL-TIGHT. LOAD SIDE TO PANEL B FROM PANEL A | |
| 08/24/2015 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/24/2015 | ELECTRIC - SERVICE UPGRADE | Denied | 1. LABEL DISCONNECTS 2. 3/4 K.O. SEAL MISSING AND TWO WIRES ON ONE LUG 3. BREAKER BLANKS MISSING 4. STRAP SEAL TIGHT TO UNIT 5. 1 1/2 STUB TO BE REMOVED AND SEALED 6. NEUTRAL TO BE IN PROPER SIZE LUG |