Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2015 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/03/2015 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/03/2015 | ELECTRIC - SERVICE UPGRADE | Denied | 1. PROVIDE SECONDARY GROUND ROD MINIMUM 6' APART FROM PRIMARY ROD 2. SECURE #4 TO BUILDING 3. BOND GAS LINE 4. PROVIDE METAL ADDRESS TAG 5. PROVIDE METAL ROOF JACK AT RISER 6. SECURE CONDUIT TO JUNCTION BOX. ***NEXT "DENIAL WILL RESULT IN A RE-FEE*** |
|
| 08/25/2015 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/25/2015 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | PROVIDE TWO GROUND RODS. DE-ENERGIZE NEW PANEL FOR INSPECTION. INCOMPLETE INSPECTION |