Permit: T15CM05735

Parcel: 11706187D


Addresses:

256 E CONGRESS ST


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T15CM05735

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
01/29/2016 MECHANICAL - HOODS Approved FINAL SMOKE TEST OK
01/20/2016 MECHANICAL - HOODS Not ready for Inspection
01/15/2016 MECHANICAL - HOODS Partial Approval PRELIMINARY SMOKE TEST PASSED. OK FOR FIRST WRAP. RE-TEST WHEN CLEANOUTS ARE INSTALLED.
01/12/2016 MECHANICAL - HOODS Cancelled IVRS - RI canceled
12/30/2015 MECHANICAL - HOODS Denied GREASE DUCT REQUIRES CLEANOUTS AT ALL ELBOWS (3).
GREASE DUCT WILL REQUIRE SMOKE TEST AND FIRE WRAP.